Summary
Site visit by NPS StaffDetails
Personnel: Jim Soldenwagner NPS
- Jim visits Hodgdon every Tuesday to maintain equipment. John knew him from his days at NPS. Jim was able to bring system back online.
- Sent Jim power troubleshooting doc.
-
The last info in the UPS log ( tail /var/log/apcupsd.events ) was from Feb 13
2025-02-13 10:50:26 +0000 Battery power exhausted.
2025-02-13 10:50:26 +0000 Initiating system shutdown!
2025-02-13 10:50:26 +0000 apcupsd exiting, signal 15
2025-02-13 10:50:26 +0000 apcupsd shutdown succeeded
2025-02-13 10:51:24 +0000 apcupsd 3.14.14 (31 May 2016) debian startup succeeded -
Stopped and restarted apcuspd. Info was logged
2025-03-26 16:07:07 +0000 apcupsd exiting, signal 15
2025-03-26 16:07:07 +0000 apcupsd shutdown succeeded
2025-03-26 16:09:06 +0000 apcupsd 3.14.14 (31 May 2016) debian startup succeeded - Tripp Lite UPS is not fully supported by apcupsd.
-
Check UPS status ( apcaccess status )
APC : 001,025,0605
DATE : 2025-03-26 15:58:09 +0000
HOSTNAME : hodgdonmdw
VERSION : 3.14.14 (31 May 2016) debian
UPSNAME : TrippLite
CABLE : USB Cable
DRIVER : USB UPS Driver
UPSMODE : Stand Alone
STARTTIME: 2025-02-13 10:51:24 +0000
MODEL : Tripp Lite UPS
STATUS : ONLINE
LOADPCT : 255.0 Percent
BCHARGE : 100.0 Percent
TIMELEFT : 68.3 Minutes
MBATTCHG : 50 Percent
MINTIMEL : 10 Minutes
MAXTIME : 0 Seconds
ALARMDEL : 30 Seconds
NUMXFERS : 0
TONBATT : 0 Seconds
CUMONBATT: 0 Seconds
XOFFBATT : N/A
SELFTEST : ??
STATFLAG : 0x05000008
SERIALNO : FW-2606 B
END APC : 2025-03-26 15:58:20 +0000